压力探测器正压送风系统的构造以及工作流程,电梯前室压差控制器型号|电梯前室压差控制器参数|电梯前室压差控制器安装
(一)、产品应用:
A、前室压力测量,电梯前室微压差压力传感器批发,前室/走道差压测控;
B、楼梯间压力测量,楼梯间/前室差压测控;
C、地下室压力测量,余压控制;
D、室内外压差检测;
电梯前室压差控制器型号|电梯前室压差控制器参数|电梯前室压差控制器安装
(一)、产品应用:
A、前室压力测量,电梯前室微压差压力传感器接线,前室/走道差压测控;
B、楼梯间压力测量,楼梯间/前室差压测控;
C、地下室压力测量,余压控制;
D、室内外压差检测;
E、门内与门外的压力大小差值检测
门内与门外的压力大小差值检测




电梯前室压力传感器

当消防前室或楼梯间的通风压力或压差超过设定值(前室25~30Pa,楼梯间40-50Pa)时,电梯前室微压差压力传感器生产厂,Working principle of itive pressure air supply pressure sensor: under normal circumstances, the itive pressure air supply fan pressurizes the air supply into the air shaft through the air duct (Green Arrow Direction) ,电梯前室微压差压力传感器, the compressed air is then sent to the front room or stairwell of each floor through the shutters or the air valve. When the ventilation pressure or pressure difference in the fire chamber or Stairwell exceeds the set value (25 ~ 30 PA in the Front Chamber and 40-50 PA in the stairwell) , the pressure sensor located on each floor immediately sends a signal to the by-pass pressure relief valve control box, the by-pass Pressure Relief Valve control box opens the by-pass pressure relief valve according to the pressure


技术参数
压力形式: 表压,压差
测量范围: 0~500pa
耐 压:1000PA
精 度: 1级
动作压力: 前室/走道动作压力:27.5Pa,复位压力:17.5PA
楼梯间/前室动作压力:45Pa,复位压力:35PA
显围:-0000~9999字,四位数字
输出方式:开关信号(24VDC/3A)
工作电压: 24VDC
介质温度:-20~85℃
密封等级:IP65
过载能力:150%FS
外形尺寸:172*112*60
重 量:350g





紫旭空调直营-电梯前室微压差压力传感器接线由武城县豪鲁邦空调设备有限公司提供。武城县豪鲁邦空调设备有限公司为客户提供“正压送风成套设备,前室压力传感器成套系统,安装升降机系列”等业务,公司拥有“豪鲁邦空调”等品牌,专注于继电器等行业。,在德州武城县鲁权屯工业园的名声不错。欢迎来电垂询,联系人:危经理。