75
Reguladores de Energía Reactiva / Reactive Power Controllers
d escripción
El regulador PFCL Elite incorpora en un solo aparato las fun-
ciones de regulador de factor de potencia, analizador de
redes y dispositivo de protección.
Mide las necesidades de energía reactiva de una instala-
ción y da las correspondientes órdenes de conexión y desco-
nexión de condensadores para mantener el cos φ prefijado.
Al mi***o tiempo permite medir los principales parámetros
de una instalación (tensión, corriente, armónicos, potencia ac-
tiva, potencia reactiva, etc.).
d esCription
PFCL Elite controller has a built in power analyzer allowing
the measurement of main electrical parameters (voltage, cu-
rrent, harmonics, active and reactive power, apparent power,
etc.). The device gives a detailed information on both, vol-
tage and current harmonic components. PFCL Elite controller
measures also ambient temperature and keeps a record of
maximum and minimum values of all measured parameters.
REGULADOR ***ANZADO
ADVANCED CONTROLLER PFCL ELITE
Código
Code
Modelo
Model
Alimentación
Power (V)
Dimensiones
Size (mm)
Escalón
Steps
PFCL06230 PFCL Elite 6 230 144 x 144 6
PFCL06400 PFCL Elite 6 400 144 x 144 6
PFCL12230 PFCL Elite 12 230 144 x 144 12
PFCL12400 PFCL Elite 12 400 144 x 144 12
PFCL06110 PFCL Elite 6 110 144 x 144 6
NUEVO
NEW
Comunicaciones de serie
El PFCL Elite dispone de puerto de comunicaciones RS-485 y
protocolo MODBUS. Esta característica permite el registro de
datos, control y supervisión remota, así como el mantenimien-
to preventivo de los equipos de compensación de reactiva,
creación de históricos y gráficos de los datos almacenados.
Función AUTO-ON-OFF
Se puede definir el modo de funcionamiento de cada paso
de condensador de forma individual.
Las opciones posibles son:
• Modo automático (Auto).
• Modo ON: condensador fijo.
• Modo OFF: condensador siempre desconectado.
Serial Communicati***
PFCL Elite controllers are equipped with RS-485 communi-
cation with MODBUS protocol. This allows the integration of
the PF regulator in a data network driven by a computer
(PC). Enables data recording, remote control, supervision and
preventive maintenance of the PF correction equipment itself
and of the whole LV network.
AUTO-ON-OFF Function
This function allows to define the operating mode of each
individual capacitor step:
• Automatic mode (Auto).
• Fixed mode (ON): Capacitor is always ON.
• Disconnected mode (OFF). Capacitor is always OFF.
上海山合海融商贸有限公司 http://76
Reguladores de Energía Reactiva / Reactive Power Controllers
PFCL ELITE REGULADOR ***ANZADO
ADVANCED CONTROLLER
Función Plug and Play
Cuando se instala un regulador de energía reactiva, es ne-
cesario configurar una serie de parámetros para el correcto
funcionamiento. Es posible que alguno de estos parámetros
sea difícil de conocer, como por ejemplo las fases de tensión
o la correspondencia de la corriente medida con su tensión,
así como la relación del transformador de corriente. El re-
gulador PFCL Elite incorpora un proceso automático que de
forma inteligente ***erigua parámetros necesarios como:
• C/K: calcula la relación entre el transformador de co-
rriente y la potencia del paso más pequeño.
• Fase: Identifica la secuencia de tensiones y la corres-
pondencia con la corriente. Es decir, identifica cual es
la U
L1
, U
L2
, U
L3
, si la corriente medida es la I
L1
, I
L2
, I
L3
y si
ésta se ha conectado al revés.
• Número de escalones instalados y Programa: me-
diante una conexión secuencial de todos los escalones,
***erigua cuantos escalones hay instalados y calcula el
programa, es decir, la relación de potencias entre los
condensadores
Control de fugas incorporado
Dispone de un circuito para medir la corriente de fuga a
tierra a tr***és de un transformador de corriente diferen-
cial. Puede medir la corriente de fuga individual de cada
condensador, lo que permite desactivarlo si es excesiva,
permitiendo la continuidad de servicio del resto de conden-
sadores.
Seguridad y mantenimiento
• Realiza una auto-revisión y muestra por pantalla la poten-
cia real de cada condensador.
• Dispone de 14 alarmas configurables, con salida de relé
conmutada incorporada (temperatura, armónicos, cos φ fue-
ra de rango, sobretensión, etc.).
• Registra el número total de maniobras realizadas por cada
contactor/condensador.
Plug and Play
A series of parameters must be configured when a power
factor regulator is installed, to make sure that it operates
correctly. Some of these parameters might be hard to know,
such as, for example, the voltage phases or the voltage co-
rresponding to the current measured, as well as the current
transformer ratio. PFCL Elite has been designed with a ***art
automatic process that detects the necessary parameters,
such as:
• C/K: calculates the ratio of the current transformer and
the power of the ***allest step.
• Phase: Identifies the voltage sequence and correspon -
dence with current. In other wo***, it identifies the U
L1
,
U
L2
, U
L3
, when the current measured is I
L1
, I
L2
, I
L3
and whe-
ther it is connected in the opposite way or not.
• Number of stages installed and Program: the system
connects all stages in a sequence, finds out how many
stages are installed and then calculates the program,
i.e., the power ratio of the capacitors.
Built-in leakage control
PFCL Elite h***e a built-in circuit to measure the earth leakage
current through a WGC transformer. The regulator is able to
measure the individual leakage of each capacitor. This allows
to disable a damaged capacitor if an excess of leakage cu-
rrent is detected without interrupting the supply service.
Safety and maintenance
• PFCL Elite performs a capacitor test every time that a ca-
pacitor step is switched ON. The real power and the leaka-
ge current of each step can be displayed.
• Up to 14 different alarm conditi*** can be programmed.
• Internal counter register which counts the number of opera-
ti*** of each individual capacitor step
上海山合海融商贸有限公司 http://77
Reguladores de Energía Reactiva / Reactive Power Controllers
PFCL ELITE REGULADOR ***ANZADO
ADVANCED CONTROLLER
Alimentación principal y medida de tensión.
400, 230, ó 110 V c.a. +15 % -10 %; 50 / 60 Hz, (ver etiqueta)
Alimentación: UL1- UL2. Medida UL1, UL2, UL3 y UN
Cables Alimentación Sección 1,5 mm2 , Fusible de protección tipo gl de 0,5 a 2 A
Circuito de medida de corriente
Transformador de corriente (TC), In /5 A c.a.,
Colocar preferiblemente en fase L1. Sección de cable mín. 2,5 mm2
Circuito de medida de corriente de fugas
Corriente nominal de secundario de transf. : I猢攀挀 = 2 mA c.a.
Transformador con relación de 500: I = 1 A c.a. +20%
Margen de medida de corriente
Corriente … I 0,05 a 5 A c.a. (sobrecarga máxima +20 %)
Corriente de fugas I: 0,01...1 A c.a. (sobrecarga máxima +20 %)
Precisión de las medidas Tensión y corriente: 1 %; cos φ : 2 % &plu***n; 1 dígito
Medida de temperatura Aprox. temperatura externa. Rango: 0...80 ºC. Precisión: &plu***n; 3 ºC
C***umo 8,2 VA (vacío) ; 9,3 VA (6 relés); 11 VA (12 relés)
Salida Relés. Contactos para Umáx. 250 V c.a., 4 A c.a., AC1.
Cableado y protección de relés de salida
Sección de cables 1,5 mm 2 ,
Protección con interruptor magnetotérmico (curva C) de 6 A o fusible tipo gl 6 A
Relé de alarma Relé conmutado de uso exclusivo para las alarmas
Normas IEC 62053-23 (2003-01) Ed. 1.0 , IEC 61326-1, EN61010-1 , UL 508
Seguridad /Aislamiento Categoría III, Clase II , según EN 61010-1
Grado de protección IP40 (equipo montado, frontal armario), IP30 (equipo sin montar) según EN-60529
Condiciones ambientales admisibles
Temperatura: -20...+60 ºC; Humedad relativa: máx. 95 % (sin condensación).
Altitud máx.: 2000 m
Sistema de control FCP (Programa que minimiza el número de maniobras)
Comunicaciones Interface: RS-tocolo: MODBUS.Velocidad: 9600, 19200, 38400
El regulador PFCL Elite mide y opera en 4 cuadrantes según el
diagrama adjunto.
Inductivo
kW -
KVAr +
cos φ -
90º
180º 0º
-90º
Capacitivo
kW -
KVAr -
cos φ -
POTENCIA
GENERADA
POTENCIA
C***UMIDA
Inductivo
kW +
KVAr +
cos φ +
Capacitivo
kW +
KVAr -
cos φ +
c aracterísticas técnicas
上海山合海融商贸有限公司 http://Reguladores de Energía Reactiva / Reactive Power Controllers
PFCL ELITE REGULADOR ***ANZADO
ADVANCED CONTROLLER
Main power supply and voltage measurement
400, 230, or 110 V a.c. +15 % -10 %; 50 / 60 Hz, (see label)
Power supply: UL1- UL2. Measurement UL1, UL2, UL3 and UN
Power supply cables Section 1,5 mm2 , gl 0.5 to 2 A protection fuse
Current measurement circuit
Current transformer (CT), In /5 A AC.,
preferably on phase L1. Min. cable section. 2.5 mm2
Leakage current measurement circuit
Nominal current of transformer secondary: I猢攀挀 = 2 mA AC.
Transformer with ratio of 500: I = 1 A AC. +20%
Current measurement margin
Current I: 0.05 ... 5 A AC (maximum overload +20%)
Leakage current I: 0.01 ... 1 A AC(maximum overload +20%)
Measurement accuracy Voltage and current: 1 %; cos φ : 2 % &plu***n; 1 digit
Temperature measurement External temperature approximation. Range: 0 ... 80ºC. Accuracy: &plu***n; 3 ºC
C***umption 8.2 VA (empty); 9.3 VA (6 relays); 11 VA (12 relays)
Output Relays. Contacts for Umax. 250 Vac., 4 A AC., AC1.
Cabling and output relay protection
Cable section 1.5 mm2,
protection with circuit breaker (C curve) of 6 A or gl 6 A fuse
Alarm relay Switched relay for use exclusively for the alarms
Standa*** IEC 62053-23 (2003-01) Ed. 1.0 , IEC 61326-1, EN61010-1 , UL 508
Safety/Insulation Category III, Class II , according to EN 61010-1
Protection degree
IP40 (equipment mounted, cabinet front panel)
IP30 (equipment not mounted) according to EN-60529
Admissible environmental conditi***
Temperature: -20 ... +60ºC; Relative humidity: max. 95% (without condensation).
Max. altitude: 2000 m
Control system FCP (a program that minimises the number of operati***)
Communicati*** Interface: RS485. Protocol: MODBUS. Speed: 9600, 19200, 38400
PFCL Elite controller measures and operates in 4 quadrants
according to the attached diagram
Inductive
kW -
KVAr +
cos φ -
90º
180º 0º
-90º
Capacitive
kW -
KVAr -
cos φ -
POWER
GENERATED
POWER
C***UMPTION
Inductive
kW +
KVAr +
cos φ +
Capacitive
kW +
KVAr -
cos φ +
t eChniCal CharaCteristiCs