Type:UL1277 VNTC control cable
Standard:UL1277,UL83,UL66,UL1581,UL1685,ICEA S-58-679,
Cores:2-61
Size: 18AWG-1000kcmil
Voltage: 600V
C***truction:
Type TC Control Cable is ***ailable in sizes 18 AWG through 10 AWG, with multiconductor c***tructi*** of 2 through 61 conductors. The product uses Type THHN or THWN conductors in sizes 14 AWG through 10 AWG and Type TFFN conductors is size 16 AWG. Individual conductors are bare annealed copper covered with a polyvinyl chloride (PVC) insulation over which a nylon (polyamide) or UL listed equal jacket is applied. The overall jacket c***ists of a heat, moisture and sunlight resistant PVC. Non-halogen jacket ***ailable upon request.
Applicati***:
Type TC Control Cable is for use in industrial power or control circuits where ***all diameter, flame retardant cables are desired. Primary installati*** include cable trays, raceways, and outdoor locati*** where supported by a messenger wire. Type TC is also listed for direct burial and for use in Class 1, Division 2 hazardous locati*** and Class 1 control circuits. C***tructi*** with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Conductors may be used at temperatures not to exceed 75°C in wet locati*** or 90°C in dry locati***.