霍尼韦尔温控器|泛达温控表|岛电温控仪
联系人:魏工 电话:15882174684
座机:028-84472033
***:2030149354
产品资料:
25°C 0.3% full scale 0.4% full scale
0 to 55°C 0.7% full scale 0.8% full scale
Set data (D/A conversion)
16-bit binary (4-digit hexadecimal)
Full scale for −10 to 10 V: E890 to 1770 hex
Full scale for other ranges: 0000 to 2EE0 hex
16-bit binary (4-digit hexadecimal)
Full scale for −10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Conversion time CP1W-MAD42: 1 ms/point (6 ms/all points)
CP1W-MAD44: 1 ms/point (8 ms/all points) 2 ms/point (6 ms/all points)
Isolation method Photocoupler isolation between analog I/O terminals and internal circuits.
No isolation between analog I/O signals.
Current c***umption
CP1W-MAD42: 5 VDC: 120 mA max., 24
VDC: 120 mA max.
CP1W-MAD44: 5 VDC: 120 mA max., 24
VDC: 170 mA max.
5 VDC: 83 mA max., 24 VDC: 110 mA max.
Item CP1W-TS001 CP1W-TS002 CP1W-TS101 CP1W-TS102
Temperature sensors
Thermocouples Platinum resistance thermometer
Switchable between K and J, but same type must be used for
all inputs.
Switchable between Pt100 and JPt100, but same type must
be used for all inputs.
Number of inputs 2424
Allocated input wo*** 2424
Accuracy (The larger of &plu***n;0.5% of converted value or &plu***n;2°C) &plu***n;1 digit
max. *
(The larger of &plu***n;0.5% of converted value or &plu***n;1°C) &plu***n;1 digit
max.
Conversion time 250 ms for 2 or 4 input points
Converted temperature data 16-bit binary data (4-digit hexadecimal)
Isolation Photocouplers between all temperature input signals
Current c***umption 5 VDC: 40 mA max., 24 VDC: 59 mA max. 5 VDC: 54 mA max., 24 VDC: 73 mA max.
Setting
CP1W-TS001/TS002 CP1W-TS101/TS102
Input type Range (°C) Range (°F) Input type Range (°C) Range (°F)
0 K −200 to 1,300 −300 to 2,300 Pt100 −200.0 to 650.0 −300.0 to 1,200.0
1 0.0 to 500.0 0.0 to 900.0 JPt100 −200.0 to 650.0 −300.0 to 1,200.0
2 J −100 to 850 −100 to 1,500 ---
3 0.0 to 400.0 0.0 to 750.0 --- Cannot be set.